D400 GC (60 Hz) Generator Set

The D400 GC diesel generator sets have been developed to meet your needs in standby applications. Producing reliable power of 400 ekW at 60 Hz, each generator set has been designed to meet ISO 8528-5 transient response requirements and built to accept 100 % rated load in one step. Our D400 GC generator sets are engineered to EPA Stationary Emergency (Tier 3) emissions standards.

Generator SpecSizer
Specifications
Equipment
Product Brochures
Units: US Metric
Generator Set Specifications
Maximum Rating
400 ekW
Minimum Rating
400 ekW
Emissions/Fuel Strategy
EPA Stationary Emergency
Voltage
480 to 600 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby
Engine Specifications
Engine Model
Cat® C13 In-line 6, 4-cycle diesel
Bore
5.1 in
130 mm
Stroke
6.2 in
157 mm
Displacement
763 in³
12.5 B
Compression Ratio
16.3:1
Aspiration
Turbocharged Air-to-Air Aftercooled
Fuel System
MEUI
Governor Type
ADEMâ„¢A4
Generator Set Dimensions
Length - Maximum
182.8 in
4625 mm
Width - Maximum
64.2 in
1630 mm
Height - Minimum
80.3 in
2039 mm
Height - Maximum
96.7 in
2456 mm
Dry Weight - Genset (minimum)
7330.4 lb
3325 kg
Dry Weight - Genset (maximum)
4107 lb
9054.4 kg
Standard Equipment
Air Inlet System
Control Panel
Cooling System
Exhaust System
Fuel System
Generator Set
Generators and Generator Attachments
Governing System
Lube System
Mounting System
Protection
Starting/Charging System
General