3516C Tier 4 Final

Producing reliable power from 1825 to 2500 ekW at 60 Hz, our 3516C diesel generator sets are made to meet your mission critical, standby and prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100% rated load in one step. Depending on the model, 3516C generator sets are EPA Stationary Emergency (Tier 2) or Tier 4 Final certified.

Generator SpecSizer
Specifications
Equipment
Product Brochures
Attachments
Units: US Metric
Generator Set Specifications
Standby Rating
2500/2000 ekW
Prime Power Rating
1825/2250 ekW
Emissions/Fuel Strategy
U.S. EPA Certified
Voltage
480 to 13800 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Mission Critical, Prime
Maximum Rating
2500 ekW
Minimum Rating
1825 ekW
Engine Specifications
Engine Model
3516C HD, ATAAC, V-16, 4-Stroke Water-Cooled Diesel
Bore
6.69 in
170 mm
Stroke
8.46 in
215 mm
Displacement
78 in
4764.73 l
Compression Ratio
14.7:1
Aspiration
TA
Fuel System
Electronic unit injection
Governor Type
ADEMâ„¢A4
Generator Set Dimensions
Length - Minimum
267.6 in
6796.6 mm
Length - Maximum
277 in
7037.5 mm
Width - Minimum
93.7 in
2378.7 mm
Width - Maximum
101.2 in
2569 mm
Height - Minimum
116.7 in
2964.8 mm
Height - Maximum
118.9 in
3019 mm
Dry Weight - Genset (minimum)
37200 lb
16874 kg
Dry Weight - Genset (maximum)
40280 lb
18270 kg
Standard Equipment
Air Inlet System
Cooling
Exhaust
Control Panels
Fuel
Generator
Power Termination
Control Panel
Cooling System
Exhaust System
Fuel System
General
Generator and Attachments
Governing System
Literature
Lubrication System
Mounting System
Starting System

Switchgear and Paralleling Controls